QSAFE INSTRUMENT
SYSTEMS PTE LTD

48 Toh Guan Road East, #08-155,
Enterprise Hub, Singapore 608586

+65 8123 4812





+65 8123 4812
ST-502 CO2 / Temperature / RH Monitor
Desktop Indoor Air Quality (IAQ) Monitor
ST-502 is a desktop indoor air quality monitor that can measure carbon dioxide, relative humidity, air temperature, and ventilation rate.
Downloads
Features
-
Non-Dispersive Infrared (NDIR) CO2 sensor ensures long term stability and durability.
-
4 Measurements-CO2/CO2 Ventilation Rate/Temperature/Humidity.
-
Large display.
-
Easy -to-use PC software for parameter settings and analysis.
-
Fast USB download.
-
CO2/Temperature/Humidity high,low alarm setting.
-
Set on the table or wall-Mounted (use 1/4”tripod nut).
-
Power adaptor AC 100V~240V to DC 12V/1.0A
Applications
-
Building HVAC Monitoring.
-
Indoor Air Quality Survey.
General Specifications
-
Read value display: Triple-display LCD monitor
-
Display unit: ℃/℉, PPM, %RH
-
Maximum value/Minimum value
-
Alarm function
-
Memory can store a maximum of 17,000 data entries.
-
Record time interval: 5 seconds/10 seconds/1 minute/5 minutes/10 minutes/30 minutes/1 hour/2 hours
-
Operating power consumption: 2.4W
-
Power adaptor AC 100V~240V to DC 12V/1.0A.
-
Internal backup battery to maintain date/time setting.
-
Operation condition: 0-50˚C (32-122˚F), 5-95%RH(non-condensing).
-
Storage temperature & Humidity: -10~60˚C (14~140˚F) ≦70%RH.
-
Supported operating systemsL XP/Windows 7/Windows 8.1/Windows 10
-
Weight: Approximately 190 grams
-
Dimensions: 89 x 62 x 128 mm (L x W x H)
Technical Specifications
-
Carbon Dioxide
-
Type: Non-dispersiveinfra-red (NDIR)
-
Measurement Ranges: 0 - 9999 PPM
-
Accuracy: ±5% of reading or ±75ppm.(0-2000ppm, others out of scale range)
-
Resolution: ±1ppm
-
Response Time: Typical 2 minutes by 90%
-
-
Temperature
-
Type: Thermistor
-
Measurement Ranges: 0℃ - 50℃ / 32˚F~122˚F
-
Accuracy: ±1.0˚C/±1.8˚F
-
Resolution: 0.1˚C/0.1˚F
-
Response Time: Typical 1 second
-
-
Relative Humidity
-
Type: Capacitive
-
Measurement Ranges: 5 - 95% RH
-
Accuracy: ±3.0%RH (20~80%); ±5.0%RH (80%)
-
Resolution: 0.1%
-
Response Time: Typical 4 seconds
-